1. Application

This product is used as power supply connection cables of portable mining equipment of rated voltage 0.66/1.14kV and below.

2. Guide to Use

The conductor temperature in normal use is 65℃ and the min. bend radius of the cables is 6 times cable diameter. The cable with yellow sheath can not be exposed to sunlight for a long time.


3. Code, Description and Usage
Code Description Usage
MY-0.38/0.66 Rubber sheathed flexible portable cable for mining use Power supply connectiion cable for 0.38/0.66kV portable mining equipment
MYP-0.38/0.66 Rubber sheathed screened flexible portable cable for mining use Power supply connectiion cable for 0.38/0.66kV portable mining equipment
MYP-0.66/1.14 Rubber sheathed screened flexible portable cable for mining use Power supply connectiion cable for 0.66/1.14kV portable mining equipment


4. Sectional Drawing


5. Technical Particulars

1) MY-0.38/0.66

No. of Cores * Sectional Area

(mm2)

Nominal Thickness (mm)

Overall Diameter

(mm)

No. of Cores * Sectional Area

(mm2)

Nominal Thickness (mm)

Overall Diameter

(mm)

Insulation Sheath Insulation Sheath
1*35 1.8 2.2 16.0-19.5 1*50 2.4 3.4 28.0-33.0
1*50 2.0 2.4 18.5-22.5 1*185 2.4 3.4 30.5-35.5
1*70 2.0 2.6 21.0-25.0 1*240 2.6 3.5 34.0-39.5
1*95 2.2 2.8 23.5-28.5 1*300 2.6 3.6 37.0-43.0
1*120 2.2 3.0 25.5-29.5 1*400 2.8 3.8 42.0-48.0

2) MY-0.38/0.66, MYP-0.66/1.14
No. of Cores * Sectional Area (mm2) Nominal Thickness (mm) Overall Diameter (mm)
Power Core Earth Core Insulation Sheath MY-0.38/0.66 MYP-0.38/0.66
3*2.5 1*2.5 1.2 3.0 16.0-18.0 19.0-22.0
3*4 1*4 1.4 3.5 19.0-22.5 22.0-26.5
3*6 1*6 1.4 3.5 21.0-25.5 24.0-29.0
3*10 1*10 1.6 4.0 25.0-30.0 28.0-32.5
1*6
3*16 1*10 1.6 4.0 27.5-32.0 30.5-35.5
1*6
3*25 1*16 1.8 4.5 32.5-37.5 35.5-41.0
1*10
3*35 1*16 1.8 4.5 33.5-41.0 38.5-44.5
1*10
3*50 1*16 2.0 5.0 41.5-47.5 44.5-51.0
3*70 1*25 2.0 5.0 46.0-53.0 49.0-56.0
3*95 1*25 2.2 5.5 52.5-59.8 55.5-63.0
3*120 1*35 2.2 5.5 56.0-63.5 59.0-67.0
3*150 1*35 2.4 6.0 62.5-70.5 65.5-74.0
3*180 1*50 2.6 6.0 64.4-75.0 67.8-76.5


3) MYP-0.66/1.14

No. of Cores * Sectional Area (mm2) Nominal Thickness (mm) Overall Diameter (mm)
Power Core Earth Core Insulation Sheath MYP-0.66/1.14
3*4 1*4 1.6 4.0 23.0-25.0
3*6 1*6 1.6 4.0 24.0-27.0
3*10 1*10 1.8 4.5 30.0-35.0
3*16 1*10 1.8 4.5 32.5-37.5
3*25 1*16 2.0 5.0 37.5-43.0
3*35 1*16 2.0 5.0 40.5-46.5
3*50 1*16 2.2 5.5 46.5-53.0
3*70 1*25 2.2 5.5 51.0-58.0
3*95 1*25 2.4 6.0 57.5-65.0
3*120 1*35 2.4 6.0 61.0-69.0
3*150 1*50 2.6 6.0 66.5-75.0
3*185 1*70★ 2.8 6.0 69.5-75.5

6. Technical Performance

1) Conductor Resistance

Power Core Sectional Area (mm2) Max. Conductor DC Resistance at 20℃ (Ω/km) Power Core Sectional Area (mm2) Max. Conductor DC Resistance at 20℃ (Ω/km)
2.5 7.98 70 0.272
4 4.95 95 0.206
6 3.30 120 0.161
10 1.91 150 0.129
16 1.21 185 0.106
25 0.780 240 0.0801
35 0.554 300 0.0641
50 0.386 400 0.0495

2) Insulation Resistance
Power Core Sectional Area (mm2) Min. Insulation Resistance at 20℃ (MΩ·km) Power Core Sectional Area (mm2) Min. Insulation Resistance at 20℃ (MΩ·km)
2.5 600 70 200
4 600 95 200
6 450 120 200
10 400 150 180
16 350 185 180
25 300 240 160
35 250 300 140
50 250 400 140

3) Max. conductor temperature in normal use: 90℃.
4) Insulation tensile strength is over 6.5MPa, and has an elongation of over 200% at break.
5) Sheath tensile strength is over 11.0MPa, and has an elongation of over 250% at break.
6) 0.38/0.66kV cables can withstand a 3.0kV/5Min voltage test and no breakdown shall occur; 0.66/1.14kV cables can withstand a 3.7kV/5Min voltage test and no breakdown shall occur.
7) The flame-retardant performance of the cable meets all requirements of burn test in standard MT 386-1995.

Other Products

  • Flexible Rubber Sheathed Coal Cutter Cables for Rated Voltage up to 1.9/3.3kV

  • 0.66/1.14kV Screened Coal Cutter Cable with Reinforced Layer and Monitoring Core

  • Flexible Coal Cutter Cables with Individual Metallic Screens of Rated Voltage up to 1.9/3.3kV

  • Flexible Frequency Converter Cable for Coalcutter of Rated Voltage 8.7/10kV and below

  • Rubber Sheathed Flexible Cable with Metallic Screen and Monitoring Core of Rated Voltage 8.7/10kV and below

  • Rubber-sheathed Flexible Portable Cables of Rated Voltage up to 6/10kV

  • Drill Cable for Mining Use of Rated Voltage 0.3/0.5KV

  • 0.3/0.5kV Light-duty Flexible Portable Cable for Mining Use

  • 0.6/1kV PVC Insulated Power Cable for Mining Use