Welcome to Lvneng Electricity Technology Co.,Ltd.

Flame-retardant Rubber Sheathed Cables for Mining Purposes

0.66/1.14kV Screened Coal Cutter Cable with Reinforced Layer and Monitoring Core

0.66/1.14kV Screened Coal Cutter Cable with Reinforced Layer and Monitoring Core

    Share:

1. Application

This product is used as power supply connection cable for coal cutters or similar equipment of rated voltage 0.66/1.14kV and below.

2. Guide to Use

The max. conductor temperature in normal use is 90℃ and the min. bend radius of the cables is 6 times cable diameter; the cable with yellow sheath can not be exposed to sunlight for a long time.

3. Code, Description and Usage
Code Description Usage
MCPJB-0.66/1.44 Rubber sheathed flexible cable for coal cutters with braided reinforced layer Power supply connection cable for coal cutters or similar equipment, can be dragged directly
MCPJR-0.66/1.44 Rubber sheathed flexible cable for coal cutters with wrapped reinforced layer Power supply connection cable for coal cutters or similar equipment, used in drag chains

4. Sectional Drawing


5. Technical Particulars

No. of Cores * Sectional Area (mm2) Insulation Thickness (mm) Sheath Thickness (mm) Overall Diameter (mm)
Power Core Earth Core Pilot Core Monitoring Core Power Core Pilot Core Inner Sheath Outer Sheath MCPJR-0.66/1.14 MCPJB-0.66/1.14
3*35 16 3*1.5 3*1.5 1.8 0.7 1.8 3.0 40.5-46.0 43.5-49.0
3*50 25 3*1.5 3*1.5 1.8 0.7 2.0 3.5 46.5-52.5 49.5-55.7
3*70 35 3*1.5 3*1.5 1.8 0.7 2.0 3.5 51.0-57.5 54.0-61.0
3* 95 50 3*1.5 3*1.5 2.0 0.7 2.4 4.0 57.5-64.5 60.5-68.0
Note: the conductor sectional area of the pilot core shall be over 1.5mm2; the inner sheath thickness is only for your information and will not be tested.


6. Technical Performance

1) The conductor resistance shall meet the following requirements
Power Core Sectional Area (mm2) Max. conductor DC resistance at 20℃ (Ω/kM) Power Core Sectional Area (mm2) Max. conductor DC resistance at 20℃ (Ω/kM)
35 0.565 70 0.277
50 0.393 95 0.210

2) The insulation resistance meets the following requirements
Nominal Sectional Area (mm2) Insulation Resistance at 20℃ (MΩ·kM) Nominal Sectional Area (mm2) Insulation Resistance at 20℃ (MΩ·kM)
35 ≥250 70 ≥200
50 ≥250 95 ≥200

3) Sheath tensile strength is over 11.0MPa, and has an elongation of over 250% at break.
4) 0.66/1.14kV cables can withstand a 3.7kV/5Min voltage test and no breakdown shall occur.
5) The flame-retardant performance of the cable meets all requirements of burn test in standard MT 386-1995.

Other Products

  • Flexible Rubber Sheathed Coal Cutter Cables for Rated Voltage up to 1.9/3.3kV

  • Flexible Coal Cutter Cables with Individual Metallic Screens of Rated Voltage up to 1.9/3.3kV

  • Flexible Frequency Converter Cable for Coalcutter of Rated Voltage 8.7/10kV and below

  • Flexible Rubber-sheathed Portable Mining Cables for Rated Voltage up to 0.66/1.14kV

  • Rubber Sheathed Flexible Cable with Metallic Screen and Monitoring Core of Rated Voltage 8.7/10kV and below

  • Rubber-sheathed Flexible Portable Cables of Rated Voltage up to 6/10kV

  • Drill Cable for Mining Use of Rated Voltage 0.3/0.5KV

  • 0.3/0.5kV Light-duty Flexible Portable Cable for Mining Use

  • 0.6/1kV PVC Insulated Power Cable for Mining Use